TLV SJ7FNB and SJ7FVB free float steam traps with thermostatic bimetal air vent. Features ductile cast iron body, up to 22 barg operating pressure, and 220 °C max temperature.

TLV SJ7FNB and SJ7FVB are reliable and durable free float steam traps with tight shut-off for use on medium-size process equipment. Models are available for horizontal (SJ7FNB) or vertical (SJ7FVB) piping installation.
| Model | SJ7FNB | SJ7FVB |
|---|---|---|
| Installation | Horizontal | Vertical |
| Connection | Flanged | Flanged |
| Size | DN 40, 50 | DN 40, 50 |
| Orifice No. | 2, 5, 9, 14, 22 | 2, 5, 9, 14, 22 |
| Maximum Operating Pressure (PMO) | 22 barg | 22 barg |
| Maximum Differential Pressure (ΔPMX) | 22 bar | 22 bar |
| Maximum Operating Temperature (TMO) | 220 °C | 220 °C |
WARNING
To avoid malfunctions, product damage, accidents or serious injury, install properly and DO NOT use this product outside the specification range. Local regulations may restrict the use of this product to below the conditions quoted.


| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Ductile Cast Iron GGG40.3 / EN 5.3103 | 0.7043 | A395 Gr.60-40-18 |
| 2 | Cover | Ductile Cast Iron GGG40.3 / EN 5.3103 | 0.7043 | A395 Gr.60-40-18 |
| 3 | Float | Stainless Steel SUS316L | 1.4404 | AISI 316L |
| 4 | Orifice | - | - | - |
| 5 | Orifice Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 6 | Screen | Stainless Steel SUS304 | 1.4301 | AISI 304 |
| 7 | Element Cover Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 8 | Cover Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 9 | Cover Bolt | Carbon Steel S45C | 1.0503 | AISI 1045 |
| 10 | Orifice Plug (SJ7FNB) | Cast Stainless Steel A351 Gr.CF8 | 1.4312 | - |
| 11 | Element Cover | Cast Stainless Steel A351 Gr.CF8 | 1.4312 | - |
| 12 | Screen Holder | Cast Stainless Steel A351 Gr.CF8 | 1.4312 | - |
| 13 | Screen Holder Gasket | Soft Iron SUYP | 1.1121 | AISI 1010 |
| 14 | Main Screen | Stainless Steel SUS430 | 1.4016 | AISI 430 |
| 15 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI 304 |
| 16 | Plug | Carbon Steel SS400 | 1.0037 | A6 |
| 17 | Element Guide | Stainless Steel SUS304 | 1.4301 | AISI 304 |
| 18 | Air Vent Valve Seat | - | - | - |
| 19 | Bimetal | - | - | - |
| 20 | Snap Ring | Stainless Steel SUS304 | 1.4301 | AISI 304 |
| 21 | Air Vent Valve | - | - | - |
| 22 | Snap Ring | Stainless Steel SUS304 | 1.4301 | AISI 304 |
| 23 | Orifice Plug Gasket (SJ7FNB) | Soft Iron SUYP | 1.1121 | AISI 1010 |

| DN | L (DIN 2501 PN25/40) | H1 | W | B | Weight (kg) |
|---|---|---|---|---|---|
| 40 | 230 | 315 | 350 | 205 | 26 |
| 50 | 230 | 315 | 350 | 205 | 28 |

| DN | L (DIN 2501 PN25/40) | W1 | B1 | Weight (kg) |
|---|---|---|---|---|
| 40 | 230 | 305 | 205 | 22 |
| 50 | 230 | 305 | 205 | 23 |

DANGER
DO NOT use this product under conditions that exceed maximum differential pressure, as condensate backup will occur!





Check to make sure that the pipes connected to the trap have been installed properly.
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.
| Part | Inspection Item |
|---|---|
| Body, Cover | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| Bimetal Unit | Check for damage |
| Screen | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Air Vent Valve Seat, Orifice | Check for rust, scale, oil film, wear or damage |
| Part | Torque (N·m) | Distance Across Flats (mm) |
|---|---|---|
| Cover Bolt | 100 | 24 |
| Orifice | 120 | 30 |
| Screen Holder | 400 | 50 |
| Drain Plug | 30 | 12 |
| Element Cover | 140 | 32 |
| Air Vent Valve Seat | 35 | 19 |
| Orifice Plug | 400 | 50 |
(Note: 1 N·m ≈ 10 kg·cm)
A visual inspection can be carried out to aid in determining the necessity for immediate maintenance or repair, if the trap is open to atmosphere.

| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping is clogged with rust or scale | Clean | |
| Steam-locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| Bimetal unit is damaged | Replace the bimetal unit | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam is discharged or leaks from the trap outlet (blowing) (steam leakage) | Rust and scale have accumulated around the orifice or under the float | Clean |
| Orifice is damaged | Replace the orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The bimetal unit is damaged, or clogged with rust or scale | Clean or replace the bimetal unit | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace with new gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |