TLV JH7.5R-X and JH7.5R-B cast steel free float steam traps with thermostatic air venting for large-size and high-pressure process equipment. Max operating pressure up to 46 barg.

TLV JH7.5R-X and JH7.5R-B are reliable and durable cast steel free float steam traps designed for use on large-size process equipment. The JH7.5R-B model is also suitable for high-pressure process equipment, handling pressures up to 46 barg and temperatures up to 425 °C. These traps discharge condensate continuously and automatically at a temperature slightly lower than the saturation temperature.

| Model | JH7.5R-X | JH7.5R-B |
|---|---|---|
| Connection | Socket Welded, Flanged | Socket Welded, Flanged |
| Size | DN 40, 50, 80 | DN 40, 50, 80 |
| Orifice No. | 2, 5, 10, 14, 22, 32 | 2, 5, 10, 14, 22, 32, 40, 46 |
| Maximum Operating Pressure (barg) PMO | 2, 5, 10, 14, 22, 32 | 2, 5, 10, 14, 22, 32, 40, 46 |
| Maximum Differential Pressure (bar) ΔPMX | 2, 5, 10, 14, 22, 32 | 2, 5, 10, 14, 22, 32, 40, 46 |
| Maximum Operating Temperature (°C) TMO | 240 | 400 / 425* |
| Type of Air Vent | X-element (6 °C subcooling) | Bimetal (vents air up to approx. 100 °C) |
With PN flange.
WARNING
PRESSURE SHELL DESIGN CONDITIONS (NOT OPERATING CONDITIONS): Maximum Allowable Pressure (barg) PMA: 40 (JH7.5R-X), 46 (JH7.5R-B) Maximum Allowable Temperature (°C) TMA: 400 / 425 To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range.

| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Cast Steel A216 Gr.WCB | 1.0619 | - |
| 2 | Cover | Carbon Steel A105 | 1.0460 | - |
| 3 | Float | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 4 | Orifice | - | - | - |
| 5 | Orifice Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 6 | Orifice Plug | Cast Stainless Steel A351 Gr.CF8 | 1.4312 | - |
| 7 | Orifice Plug Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 8 | Screen | Stainless Steel SUS430 | 1.4016 | AISI430 |
| 9 | Screen Holder | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 10 | Snap Ring | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 11 | Cover Gasket | Graphite/Stainless Steel SUS304 | -/1.4301 | -/AISI304 |
| 12 | Cover Bolt | Alloy Steel SNB16 | 1.7711 | A193 Gr.B16 |
| 13 | Cover Nut | Carbon Steel S45C | 1.0503 | AISI1045 |
| 16 | Socket/Flange (DN 40, 50) | Carbon Steel A105 | 1.0460 | - |
| 16 | Flange (DN 80) | Cast Steel A216 Gr.WCB | 1.0619 | - |
| 17 | Air Vent Unit | - | - | - |
| 18 | Air Vent Unit Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 19 | Air Vent Guide | Stainless Steel SUS303 | 1.4305 | AISI303 |
| 20 | Drain Plug Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 21 | Drain Plug | Carbon Steel S25C | 1.0460 | AISI1025 |

| DN | L (mm) | H (mm) | H1 (mm) | φW (mm) | φD (mm) | φC (mm) | h (mm) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 40 | 466 | 389 | 291 | 305 | 64 | 48.8 | 13 | 51 |
| 50 | 466 | 389 | 291 | 305 | 77.5 | 61.2 | 16 | 56 |
| 80 | 506 | 389 | 291 | 305 | 112 | 89.8 | - | 65 |

| DN | L (DIN PN25/40) | L (ASME 150RF) | L (ASME 300RF) | L (ASME 600RF) | H (mm) | H1 (mm) | φW (mm) | Weight (kg)* |
|---|---|---|---|---|---|---|---|---|
| 40 | 472 | 471 | 478 | 494 | 389 | 291 | 305 | 60 |
| 50 | 476 | 475 | 481 | 500 | 389 | 291 | 305 | 62 |
| 80 | 504 | 504 | 514 | 533 | 389 | 291 | 305 | 68 |
Weight is for DIN PN 25/40.
DANGER
Do not use traps under conditions that exceed maximum differential pressure, as condensate backup will occur!



Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.
| Part | Torque (N·m) | Distance Across Flats (mm) |
|---|---|---|
| Cover Nut | 200 | 30 |
| Orifice | 600 | 46 |
| Orifice Plug | 800 | 46 |
| Drain Plug | 100 | 26 |
| Air Vent Valve Seat | 30 | 19 |
| Air Vent Guide | 150 | 30 |
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| The bimetal is damaged | Replace with new bimetal | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| Steam is discharged or leaks from the trap outlet (blowing) (steam leakage) | Rust and scale have accumulated around the valve seat or under the float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The bimetal air vent valve surface and/or the air vent valve seat has a build-up or is scratched | Clean or replace with new bimetal and/or air vent valve seat | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace the gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |