TLV JH7RL-B free float steam trap with thermostatic bimetal air vent. Suitable for heat exchangers, process heaters, and coils up to 10 MPaG.

The TLV JH7RL-B is an inline repairable free float steam trap equipped with a thermostatic bimetal air vent. It is designed for applications requiring small-to-large capacities and can handle pressures up to 10 MPaG (1500 psig). Typical applications include various types of heat exchangers, process heaters, and coils. The trap discharges condensate continuously and automatically at a temperature slightly lower than the saturation temperature.
The steam trap consists of several key components including the body, free float mechanism, orifice, thermostatic air venting components, and screens to protect internal mechanisms.

WARNING
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions.
| Part | Parts Inspection Procedure |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| Bimetal Plate | Check for damage |
| Air Vent Valve (and Seat) | Check for damage |
| Screen(s) | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Orifice Opening | Check for rust, scale, oil film, wear or damage |
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| The bimetal is damaged | Replace with new bimetal | |
| Trap operating pressure exceeds max specified, or insufficient pressure diff | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through bypass or close inlet valve and cool | |
| Steam is discharged or leaks from the trap outlet (blowing / steam leakage) | Rust and scale have accumulated around valve seat or under float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| Bimetal air vent valve surface/seat has build-up or is scratched | Clean or replace with new bimetal and/or seat | |
| The bimetal is damaged | Replace with new bimetal |