Inline RepairableBimetal Air Vent

TLV JH7RL-B Free Float Steam Trap

TLV JH7RL-B free float steam trap with thermostatic bimetal air vent. Suitable for heat exchangers, process heaters, and coils up to 10 MPaG.

TLV JH7RL-B Free Float Steam Trap

The TLV JH7RL-B is an inline repairable free float steam trap equipped with a thermostatic bimetal air vent. It is designed for applications requiring small-to-large capacities and can handle pressures up to 10 MPaG (1500 psig). Typical applications include various types of heat exchangers, process heaters, and coils. The trap discharges condensate continuously and automatically at a temperature slightly lower than the saturation temperature.

Configuration

The steam trap consists of several key components including the body, free float mechanism, orifice, thermostatic air venting components, and screens to protect internal mechanisms.

TLV JH7RL-B cross section configuration

WARNING

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.

Proper Installation

  • Install for use under conditions in which no freeze-up will occur.
  • Install for use under conditions in which no water hammer will occur.
  • Before installation, be sure to remove all protective seals and blow out the inlet piping to remove dirt and oil.
  • Install the steam trap within the allowable inclination and make sure the arrow mark on the body corresponds with the direction of flow.
  • Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity.
  • Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  • Install a bypass valve, as well as inlet and outlet isolation valves.

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions.

Parts Inspection Procedure

PartParts Inspection Procedure
Body, Cover(s)Check inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
Bimetal PlateCheck for damage
Air Vent Valve (and Seat)Check for damage
Screen(s)Check for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Orifice OpeningCheck for rust, scale, oil film, wear or damage

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked) or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping are clogged with rust or scaleClean
The bimetal is damagedReplace with new bimetal
Trap operating pressure exceeds max specified, or insufficient pressure diffCompare specifications and actual operating conditions
Steam locking has occurredBlowdown through bypass or close inlet valve and cool
Steam is discharged or leaks from the trap outlet (blowing / steam leakage)Rust and scale have accumulated around valve seat or under floatClean
Orifice is damagedReplace with new orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
Bimetal air vent valve surface/seat has build-up or is scratchedClean or replace with new bimetal and/or seat
The bimetal is damagedReplace with new bimetal