TLV JH7.2R-X and JH7.2R-B free float steam traps with thermostatic air venting. Cast steel construction for medium-size and high-pressure process equipment, handling pressures up to 46 barg and temperatures up to 425°C.

TLV JH7.2R-X and JH7.2R-B are reliable and durable cast steel free float steam traps designed for use on medium-size process equipment. The JH7.2R-B model is also suitable for high-pressure process applications. These inline repairable steam traps discharge condensate continuously and automatically at a temperature slightly lower than the saturation temperature.

WARNING
Maximum allowable pressure (PMA) is 46 barg and maximum allowable temperature (TMA) is 400 °C / 425 °C. These are PRESSURE SHELL DESIGN CONDITIONS, NOT OPERATING CONDITIONS. To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range.
| Model | JH7.2R-X | JH7.2R-B |
|---|---|---|
| Connection | Socket Welded, Flanged | Socket Welded, Flanged |
| Size | DN 40, 50 | DN 40, 50 |
| Orifice No. | 2, 5, 10, 14, 22, 32 | 2, 5, 10, 14, 22, 32, 40, 46 |
| Maximum Operating Pressure (PMO) | 2, 5, 10, 14, 22, 32 barg | 2, 5, 10, 14, 22, 32, 40, 46 barg |
| Maximum Differential Pressure (ΔPMX) | 2, 5, 10, 14, 22, 32 bar | 2, 5, 10, 14, 22, 32, 40, 46 bar |
| Maximum Operating Temperature (TMO) | 240 °C | 400 °C / 425 °C* |
| Type of Air Vent | X-element (6 °C subcooling) | Bimetal (vents air up to approx. 100 °C) |
* With PN flange

| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Cast Steel A216 Gr.WCB | 1.0619 | — |
| 2 | Cover | Carbon Steel A105 | 1.0460 | — |
| 3 | Float | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 5 | Orifice Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 6 | Orifice Plug | Cast Stainless Steel A351 Gr.CF8 | 1.4312 | — |
| 8 | Screen inside/outside | Stainless Steel SUS430/304 | 1.4016/1.4301 | AISI430/304 |

| DN | L (mm) | H (mm) | H1 (mm) | W (mm) | h (mm) | Weight (kg) |
|---|---|---|---|---|---|---|
| 40 | 401 | 320 | 244 | 250 | 13 | 35 |
| 50 | 401 | 320 | 244 | 250 | 16 | 38 |

| DN | L (DIN PN25/40) | L (ASME 150RF) | L (ASME 300RF) | L (ASME 600RF) | H | H1 | W | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 40 | 407 | 406 | 413 | 429 | 320 | 244 | 250 | 35 |
| 50 | 411 | 410 | 416 | 435 | 320 | 244 | 250 | 40 |
JH7.2R-X
JH7.2R-B
INFO
DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.
Check to make sure that the pipes connected to the trap have been installed properly:
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
| Parts Inspection Procedure | |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| X-element | Check for damage |
| Screen(s) | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Air Vent Valve Seat, Orifice | Check for rust, scale, oil film, wear or damage |
If the expected performance is unachievable after installation of the steam trap, check the following points for appropriate corrective measures.
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| X-element is damaged | Replace the X-element | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| Steam is discharged or leaks from the trap outlet (blowing / steam leakage) | Rust and scale have accumulated around the orifice or under the float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The X-element is damaged, or clogged with rust or scale. | Clean or replace the X-element | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace the gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |