Free FloatThermostatic Air VentMax 2.1 MPaG

TLV J8X Free Float Steam Trap

TLV J8X cast iron free float steam trap with thermostatic air venting, suitable for tracer lines, heaters, and heat exchangers up to 2.1 MPaG.

TLV J8X Free Float Steam Trap

The TLV J8X is a free float steam trap with a thermostatic air vent (X-element). It is suitable for a wide range of applications up to 2.1 MPaG (300 psig), such as tracer lines, unit and process heaters, heating coils, heat exchangers, etc. The trap discharges condensate continuously and automatically, at a temperature slightly lower than saturation temperature.

Configuration

TLV J8X cross-section configuration

No.DescriptionNo.Description
1Body15X-element Guide
2Cover16Spring Clip
3Cover Gasket17X-element Cover
4Float18Snap-Ring
5Orifice19Drain Plug*
6Orifice O-Ring20Drain Plug Gasket*
7Orifice Holder Plug21Air Vent Valve Seat
8Orifice Plug Gasket22Connector
9Screen23Cover Bolt
10Screen Holder24Plug
11Screen Holder Retainer25Plug Gasket
12Float Cover26Flange
13Snap-Ring27Pipe
14X-element28Nameplate

*Option

Exploded View

TLV J8X exploded view and parts

Proper Installation

WARNING

  • Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/closing should be carried out only by trained maintenance personnel.
  • Take measures to prevent people from coming into direct contact with product outlets.
  • Install for use under conditions in which no freeze-up will occur.
  • Install for use under conditions in which no water hammer will occur.
  1. Before installation, be sure to remove all protective seals.
  2. Before installing the trap, blow out the inlet piping to remove all dirt and oil.
  3. When hoisting the product, hang the rope around the inlet/outlet as close to the body as possible.
  4. Install the steam trap within the allowable inclination, as shown below. Also make sure that the arrow mark on the body corresponds with the direction of flow.
  5. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
  6. Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  7. Install a bypass valve to discharge condensate, and inlet and outlet valves to isolate the trap in the event of trap failure or when performing maintenance.
  8. Install a check valve at the trap outlet whenever more than one trap is connected to the condensate collection pipeline.

Allowable Inclination

TLV J8X allowable vertical inclination

TLV J8X allowable horizontal inclination

Piping Arrangement

Check to make sure that the pipes connected to the trap have been installed properly:

  1. Is the pipe diameter suitable?
  2. Has the trap been installed within the allowable inclination and with the arrow on the body pointing in the direction of flow?
  3. Has sufficient space been secured for maintenance?
  4. Have maintenance valves been installed at inlet and outlet? If the outlet is subject to back pressure, has a check valve been installed?
  5. Is the inlet pipe as short as possible, with as few bends as possible, and installed so that the condensate will flow naturally down into the trap?

TLV J8X correct and incorrect piping arrangements

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in a temperature drop in the equipment, poor product quality or losses due to steam leakage.

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.

Parts Inspection Procedure

PartInspection
Body, CoverCheck inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
X-elementCheck for damage
ScreenCheck for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Air Vent Valve Seat, OrificeCheck for rust, scale, oil film, wear or damage

Tightening Torque and Distance Across Flats for J8X

PartTorqueDistance Across Flats
Cover Bolt250 N·m (185 lbf·ft)32 mm (1 1/4 in)
Air Vent Valve Seat35 N·m (26 lbf·ft)19 mm (3/4 in)
Plug30 N·m (22 lbf·ft)*12 mm (1 5/32 in)
Orifice Holder Plug800 N·m (590 lbf·ft)105 mm (4 1/8 in)
Drain Plug40 N·m (29 lbf·ft)*14 mm (9/16 in)

*Indicates torque values with a sealing tape wrapped 3 – 3.5 times around the threads of the plug or drain plug.

Operational Check

A visual inspection can be carried out to aid in determining the necessity for immediate maintenance or repair, if the trap is open to atmosphere. If the trap does not discharge to atmosphere, use diagnostic equipment.

StateDescription
NormalCondensate is discharged continuously with flash steam and the sound of flow can be heard.
BlockedNo condensate is discharged. The trap is quiet and makes no noise, and the surface temperature of the trap is low.
BlowingLive steam continually flows from the outlet and there is a continuous metallic sound.
Steam LeakageLive steam is discharged through the trap outlet together with the condensate and there is a high-pitched sound.

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked) or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping is clogged with rust or scaleClean
Steam-locking has occurredBlowdown through the bypass or close the trap inlet valve and allow the trap to cool
X-element is damagedReplace the X-element
The trap operating pressure exceeds the maximum specified pressureCompare specifications and actual operating conditions
Steam is discharged or leaks from the trap outlet (blowing / steam leakage)Rust and scale have accumulated around the orifice or under the floatClean
Orifice is damagedReplace the orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
The X-element is damaged, or clogged with rust or scaleClean or replace the X-element
Steam leaks from a place other than the trap outletDeterioration of or damage to gasketsReplace with new gaskets
Leakage from eroded cavities of body or coverReplace the trap
Improper tightening torque for cover was usedTighten to the proper torque
Float is frequently damagedWater hammer occursExamine the piping for problems that can cause water hammer