Skip to content
Forged Carbon SteelMax 32 barMax 250°C

Armstrong EM Forged Steel Inverted Bucket Steam Trap

Armstrong EM forged steel inverted bucket steam trap. Features a frictionless free-floating guided lever, stainless steel internals, and handles up to 32 bar at 250°C.

Armstrong EM Forged Steel Inverted Bucket Steam Trap

Armstrong EM forged steel inverted bucket steam trap combines the most reliable steam trap operating principle known in a body, which can be opened for easy maintenance. It offers high resistance to wear, corrosion, and water hammer.

The free-floating guided lever valve mechanism is "frictionless" with all wear points heavily reinforced. All working parts are stainless steel; the valve and seat are hardened chrome steel, individually ground and lapped.

Features and Operation

  • Freedom from dirt problems: Condensate flow under the bottom edge of the bucket keeps sediment and "sludge" in suspension until discharged by full differential purging action. The valve orifice opens wide and closes tight. There is no buildup of dirt, and no close clearances to be affected by scale. Under normal conditions of reasonably "clean steam", a strainer is not necessary. However, this is left to the user's discretion.
  • Air handling ability: A vent in the bucket top provides continuous automatic air and CO2 venting with no cooling leg and prevents air binding. A wiggle wire ensures a clean vent hole at all times. Any steam passing through the vent is condensed and discharged as liquid.
  • No steam loss: Steam does not reach the water-sealed valve. Inverted bucket traps require no adjustment and no live steam to operate.

Armstrong EM inverted bucket steam trap cross section

Materials

ComponentMaterial
BodyForged carbon steel
InternalsAll stainless steel – 304
Valve and seatHardened chrome steel – 440F
GasketSpiral wounded graphite
Bolts24 CrMo5

Options

  • Bucket vent scrubbing wire for heavy dirt/oil conditions
  • For superheated steam, stellited valve and seat are advised

Dimensions and Weights

Model EM Side Inlet, Side Outlet Trap (dimensions in mm)

Armstrong EM side inlet side outlet trap dimensions

Pipe Connections1/2 in (15 mm)3/4 in (20 mm)1 in (25 mm)
"C" Face-to-Face (screwed & SW)92 mm92 mm
"CC" Face-to-Face (flanged ANSI CL150)171 mm178 mm184 mm
"CC" Face-to-Face (flanged ANSI CL300)178 mm187 mm197 mm
"D" Bottom to C Inlet189 mm189 mm189 mm
"B" Height (screwed & SW)210 mm210 mm
"BB" Height (flanged*)235 mm240 mm245 mm
Weight, screwed3.1 kg3.1 kg
Weight, flanged5.5 kg7.1 kg8.1 kg

Maintenance

WARNING

Equipment under pressure - Operating temperature > 100°C. Make sure the trap is cold before handling!

Mechanism Adjustment

The mechanism should be adjusted as shown below. When correctly aligned, lever (B) can be moved sideways the same distance to the right as to the left. If guide pin (A) is not in the middle of the orifices, adjust by slightly hitting with a hammer.

Armstrong EM correct mechanism adjustmentArmstrong EM incorrect mechanism adjustment

Internals Maintenance

  1. Unscrew bolts (11) and nuts (10) and lift the cap (1). Body (2) can remain connected to the steam line.
  2. Clean or replace bucket (6) or mechanism (valve and seat) (3, 4 & 5).
  3. Replace gasket (7).
  4. Put the cap (1) back on the body (2) and screw bolts (11) and nuts (10).

Armstrong EM internals maintenance diagram