Armstrong CD-40 and CD-60 Series controlled disc steam traps feature a replaceable capsule, steam jacket heating chamber, and capacities up to 2,850 lb/hr.

Armstrong CD-40 and CD-60 Series controlled disc steam traps contain a replaceable capsule, making it possible to renew a worn trap by simply replacing the capsule. A heating chamber in the shell ensures consistent operation. This steam jacket provides a relatively constant temperature in the control chamber regardless of ambient conditions. Cycling rate is controlled and does not increase when the trap is exposed to cold winds, rain or snow.

CD-40 Series traps are also available with optional integral .045 perforated stainless steel strainer screens. CD-60 Series traps contain integral strainers with ratios of open area to inside area of pipe that equal or exceed those of most separate “Y” type strainers.

Maximum allowable pressure (vessel design):
Maximum operating pressure: 600 psig (41 barg) at saturated steam temperature Minimum operating pressure: 10 psig (0.7 barg)
| Component | Model CD-40 | Model CD-60 |
|---|---|---|
| Body | Carbon steel—C-1215 | ASTM A216 WCB |
| Cap | — | ASTM A216 WCB |
| Control chamber | Hardened stainless steel | Hardened stainless steel |
| Disc | Hardened stainless steel | Hardened stainless steel |
| Capsule body | Hardened stainless steel | Hardened stainless steel |
| Strainer screen | Stainless steel (option) | 20 x 20 mesh stainless steel |
| Model No. | Pipe Connections | "A" (Diameter) | "B" (Height) | "C" (Length) | "D" (C to Top of Cap) | Weight |
|---|---|---|---|---|---|---|
| CD-41* | 3/8", 1/2" (10, 15 mm) | 1-1/4" (31.7 mm) | — | 3" (76.2 mm), 3-13/32" (86.5 mm) | — | 3/4 lb (0.3 kg) |
| CD-42* | 3/4" (20 mm) | 1-5/8" (41.3 mm) | — | 3-15/16" (100.0 mm) | — | 1-3/4 lb (0.8 kg) |
| CD-43* | 1" (25 mm) | 2-3/8" (60.3 mm) | — | 4-5/8" (117.5 mm) | — | 4-1/4 lb (1.9 kg) |
| CD-61 | 3/8", 1/2" (10, 15 mm) | — | 2-3/4" (66.7 mm) | 3-1/2" (88.9 mm) | 2-1/8" (50.8 mm) | 2-3/4 lb (1.2 kg), 2-1/2 lb (1.1 kg) |
| CD-62 | 3/4" (20 mm) | — | 3-1/2" (87.3 mm) | 4-5/8" (117 mm) | 2-3/4" (68.3 mm) | 4-3/4 lb (2.2 kg) |
| CD-63 | 1" (25 mm) | — | 4-1/4" (108 mm) | 4-3/4" (122 mm) | 3-5/16" (84.1 mm) | 6-3/4 lb (3.1 kg) |
*Optional integral strainer available.

Capacities given are continuous discharge capacities in pounds and kilograms of hot condensate per hour at pressure differential indicated with condensate temperatures approximately 25°F (14°C) below steam temperatures.
Operating Note
CD traps can operate with a minimum of 2 psig (0.15 barg) inlet pressure and a maximum of 80% back pressure. However, for best results, inlet pressure should not drop below 10 psig (0.70 barg) and back pressure should not exceed 50% of inlet pressure.