TLV SJ6FNX and SJ6FVX ductile cast iron free float steam traps with thermostatic air venting. Designed for medium process equipment up to 22 barg.

TLV SJ6FNX and SJ6FVX are reliable and durable ductile cast iron free float steam traps with tight shut-off for use on medium process equipment. The SJ6FNX is designed for horizontal piping installation, while the SJ6FVX is designed for vertical piping installation.
Features include a self-modulating free float that provides continuous, smooth, low-velocity condensate discharge as process loads vary. The precision-ground float, constant water seal, and three-point seating design ensure a steam-tight seal, even under no-load conditions. A thermostatic capsule (X-element) with a "fail open" feature vents air automatically until close-to-steam temperature. The built-in screen with a large surface area ensures extended trouble-free operation, and easy inline access to internal parts simplifies cleaning and reduces maintenance costs.
| Model | SJ6FNX | SJ6FVX |
|---|---|---|
| Installation | Horizontal | Vertical |
| Connection | Flanged | Flanged |
| Size | DN 40, 50 | DN 40, 50 |
| Orifice No. | 2, 5, 9, 14, 22 | 2, 5, 9, 14, 22 |
| Maximum Operating Pressure (PMO) | 2, 5, 9, 14, 22 barg | 2, 5, 9, 14, 22 barg |
| Maximum Differential Pressure (ΔPMX) | 2, 5, 9, 14, 22 bar | 2, 5, 9, 14, 22 bar |
| Maximum Operating Temperature (TMO) | 220 °C | 220 °C |
| Subcooling of X-element Fill | up to 6 °C | up to 6 °C |
| Type of X-element | C6 | C6 |
WARNING
To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range. Maximum Allowable Temperature (TMA) is 220 °C. Minimum Allowable Temperature is 0 °C.

| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Ductile Cast Iron (EN-GJS-400-18-LT) | 0.7043 | A395 Gr.60-40-18 |
| 2 | Cover | Ductile Cast Iron (EN-GJS-400-18-LT) | 0.7043 | A395 Gr.60-40-18 |
| 3 | Cover Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 4 | Float | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 5 | Orifice | - | - | - |
| 6 | Orifice Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 7 | X-element Screen | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 8 | Screen | Stainless Steel SUS430 | 1.4016 | AISI430 |
| 9 | Screen Holder | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | - |
| 10 | Screen Holder Gasket | Soft Iron SUYP | 1.1121 | AISI1010 |
| 11 | Orifice Plug (SJ6FNX) | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | - |
| 12 | Orifice Plug Gasket (SJ6FNX) | Soft Iron SUYP | 1.1121 | AISI1010 |
| 13 | Drain Plug | Carbon Steel SS400 | 1.0037 | A6 |
| 14 | X-element | Stainless Steel | - | - |
| 15 | X-element Guide | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 16 | X-element Cover | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | - |
| 17 | Air Vent Valve Seat | Stainless Steel SUS420F | 1.4028 | AISI420F |
| 18 | Cover Bolt | Carbon Steel S45C | 1.0503 | AISI1045 |
| 19 | Spring Clip | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 20 | X-element Cover Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 21 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |

| DN | L (DIN 2501 PN25/40) | H1 | W | B | Weight (kg) |
|---|---|---|---|---|---|
| 40 | 230 mm | 268 mm | 311 mm | 176 mm | 22 |
| 50 | 230 mm | 268 mm | 311 mm | 176 mm | 24 |

| DN | L (DIN 2501 PN25/40) | W1 | B | Weight (kg) |
|---|---|---|---|---|
| 40 | 230 mm | 263 mm | 176 mm | 17 |
| 50 | 230 mm | 263 mm | 176 mm | 18 |

DANGER
DO NOT use this product under conditions that exceed maximum differential pressure, as condensate backup will occur!
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.
| Part | Torque (N·m) | Distance Across Flats (mm) |
|---|---|---|
| Cover Bolt | 90 | 22 |
| Orifice | 120 | 30 |
| Screen Holder | 400 | 50 |
| Drain Plug | 30 | 12 |
| X-element Cover | 140 | 32 |
| Air Vent Valve Seat | 35 | 19 |
| Orifice Plug (SJ6FNX) | 400 | 50 |
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping is clogged with rust or scale | Clean | |
| Steam-locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| X-element is damaged | Replace the X-element | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam is discharged or leaks from the trap outlet | Rust and scale have accumulated around the orifice or under the float | Clean |
| Orifice is damaged | Replace the orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The X-element is damaged, or clogged with rust or scale | Clean or replace the X-element | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace with new gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |