TLV JH7RH-B low alloy cast steel free float steam trap with thermostatic bimetal air vent. Suitable for medium-size process equipment, superheated and high-pressure applications up to 120 barg.

The TLV JH7RH-B is a reliable and durable low alloy cast steel free float steam trap designed for use on medium-size process equipment. It is suitable for both superheated and extremely high-pressure applications up to 120 barg.
Options
For higher pressure and temperature applications, the JH7RH-P and JH7RH-W are manufactured with a cover threaded plug or socket connection instead of the bimetal air vent, allowing operation up to 530 °C.

| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Low Alloy Cast Steel A217 Gr.WC9 | 1.7379 | - |
| 2 | Cover | Low Alloy Cast Steel A217 Gr.WC9 | 1.7379 | - |
| 3 | Float | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 4 | Orifice | - | - | - |
| 5 | Orifice Gasket | Graphite/Stainless Steel SUS316 | -/1.4401 | -/AISI316 |
| 6 | Orifice Locknut | Stainless Steel SUS303 | 1.4305 | AISI303 |
| 7 | Outlet Cover Gasket | Graphite/Stainless Steel SUS309S+cb | - | - |
| 8 | Outlet Cover | Stainless Steel SUS420J2 | 1.4031 | AISI420 |
| 9 | Cover Bolt | Alloy Steel SNB16 | 1.7711 | A193 Gr.B16 |
| 10 | Cover Nut | Alloy Steel SNB7 | 1.7225 | A193 Gr.B7 |
| 11 | Cover Gasket | Graphite/Stainless Steel SUS309S+cb | - | - |
| 12 | Outlet Cover Bolt | Alloy Steel SNB16 | 1.7711 | A193 Gr.B16 |
| 13 | Outlet Cover Nut | Alloy Steel SNB7 | 1.7225 | A193 Gr.B7 |
| 14 | Screen | Stainless Steel SUS430 | 1.4016 | AISI430 |
| 15 | Screen Holder | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 16 | Snap Ring | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 17 | Screen Holder Retainer | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 18 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 19 | Bimetal Air Vent Unit | - | - | - |
| 20 | Air Vent Guide | Stainless Steel SUS303 | 1.4305 | AISI303 |
| 21 | Air Vent Unit Gasket | Stainless Steel SUS316L | 1.4404 | AISI316L |

| DN | L (mm) | H (mm) | H1 (mm) | φW (mm) | φD (mm) | φC (mm) | h (mm) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 15 | 390 | 371 (382) | 270 | 258 | 53.5 | 21.8 | 13 | 76 |
| 20 | 390 | 371 (382) | 270 | 258 | 53.5 | 27.2 | 13 | 76 |
| 25 | 390 | 371 (382) | 270 | 258 | 53.5 | 33.9 | 13 | 76 |
| ( ) JH7RH-W |

| DN | L (ASME Class 900RF/1500RF) (mm) | H (mm) | H1 (mm) | φW (mm) | Weight (kg) |
|---|---|---|---|---|---|
| 15 | 572 | 371 (382) | 270 | 258 | 94 |
| 20 | 572 | 371 (382) | 270 | 258 | 95 |
| 25 | 572 | 371 (382) | 270 | 258 | 98 |
| ( ) JH7RH-W |

WARNING
DO NOT use traps under conditions that exceed maximum differential pressure, as condensate backup will occur!
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.
Parts Inspection Procedure
| Part | Inspection Item |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| Bimetal Plate | Check for damage |
| Air Vent Valve (and Seat) | Check for damage |
| Screen(s) | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Orifice Opening | Check for rust, scale, oil film, wear or damage |
Tightening Torques (JH7RH-B)
| Part | Torque (N·m) | Distance Across Flats (mm) |
|---|---|---|
| Cover Nut | 700 | 46 |
| Outlet Cover Nut | 200 | 30 |
| Orifice Locknut | 250 | 32 |
| Air Vent Valve Seat | 30 | 19 |
| Air Vent Guide | 100 | 24 |
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| The bimetal is damaged | Replace with new bimetal | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| Steam is discharged or leaks from the trap outlet (blowing) (steam leakage) | Rust and scale have accumulated around the valve seat or under the float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The bimetal air vent valve surface and/or the air vent valve seat has a build-up or is scratched | Clean or replace with new bimetal and/or air vent valve seat | |
| The bimetal is damaged | Replace with new bimetal | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace the gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |