Burkert 337029 Type 6014 direct-acting 3/2-way plunger solenoid valve. Features a stainless steel body, NPT 1/4 connection, 2.0mm orifice, 24V DC, and FKM seal for 0-10 bar.

Burkert 337029 Type 6014 is a direct-acting, compact 3/2-way plunger solenoid valve. The stopper and core guide tube are welded together to enhance pressure resistance and leak-tightness. This specific model features a stainless steel body, FKM seals, a 2.0 mm orifice, and an NPT 1/4 port connection. It operates on 24 V DC and is designed for a pressure range of 0 to 10 bar.
| Symbol | Description |
|---|---|
![]() | Circuit function C (CF C) 3/2-way solenoid valve Direct-acting Normally closed |
| Product properties | |
|---|---|
| Seal | FKM |
| Body | Stainless steel |
| Coil | Polyamide |
| Orifice | DN 2.0 |
| Circuit function | C (Normally closed) |
| Thermal insulation class | Polyamide coil class B |
| Operating voltage | 24 V DC |
| Voltage tolerance | ±10% |
| Operating medium | Technical vacuum, neutral gases and liquids (e.g. compressed air, town gas, natural gas, water, hydraulic oil, petrol) |
| Medium temperature | -10 °C...+100 °C |
| Viscosity | Max. 21 mm²/s |
| Electrical connection | Plug contacts according to DIN EN 175301-803 form A |
| Port connection | NPT 1/4 |
| Degree of protection | IP65 with cable plug Type 2518 |
| Installation position | As required, preferably with actuator upright |
| Ambient temperature | Max. +55 °C |

| No. | Element | Material |
|---|---|---|
| 1 | Stopper | Stainless steel 1.4105/430F |
| 2 | Shading ring | Ag (stainless steel variant) |
| 3 | Plunger seal | FKM |
| 4 | Spring | Stainless steel 1.4310/301 |
| 5 | Magnetic core | Stainless steel 1.4105/430F |
| 6 | Core guide tube | Stainless steel 1.4303/305/308 |
| 7 | O-ring | FKM |
| 8 | Plunger seal | FKM |
| 9 | Valve body | Stainless steel 1.4305/303 or 1.4401/316 |
| 10 | Spring | Stainless steel 1.4310/301 |
| 11 | Sub-base | Stainless steel 1.4301/304 |
| 12 | Coil | PA (Polyamide) |
| 13 | Nut | Stainless steel 1.4305/303 PTFE coated |
INFO
Dimensions in mm


| Port connection | A [inch] | B [mm] | C [mm] | D [mm] | G [mm] |
|---|---|---|---|---|---|
| Threaded without manual override | G 1/4 | 46 | 26.8 | 49 | 12 |
| Coil size | E [mm] | F [mm] |
|---|---|---|
| 5 | 32 | 45 |
| 6 | 40 | 51 |
For the positions marked with *, ** or *** in the drawing, the connections are marked with the letters shown in the table below, depending on the circuit function. Unused circuit functions A or B connections will be closed off with a blanking plug or cap nut.
| Circuit function | * | ** | *** |
|---|---|---|---|
| A | P | blank off | A |
| B | blank off | B | P |
| C | P | R | A |
| D | R | P | B |
| T | P | R | A |
| Orifice [mm] | Coil power [W] | Power consumption Inrush AC [VA] | Power consumption Hold AC [VA/W] | Response times Opening [ms] | Response times Closing [ms] |
|---|---|---|---|---|---|
| 2.0 | 8 W AC or 8 W DC | 24 | 8 | 10...15 | 15...20 |
Measurement at +20 °C, 6 bar at the valve outlet, opening: pressure build-up 0...90 %, closing: pressure reduction 100...10 %
Explore similar products in our catalog