BURKERT 20121702 Type 8640 16-Bank Modular Pneumatic Valve Island (G 1/2, G 1/4, 3/2-Way)

BURKERT 20121702 (Type 8640) is a 16-bank modular pneumatic valve island with 33 mm width, G 1/2 supply, G 1/4 ports, 3/2 valve function, 2 to 8 bar pressure range, and DIN-rail mounting.

BURKERT 20121702 Type 8640 16-Bank Modular Pneumatic Valve Island (G 1/2, G 1/4, 3/2-Way)

BURKERT 20121702 (Type 8640) is a 16-bank modular pneumatic valve island configured with a 33 mm station width, G 1/2 pressure supply ports, and G 1/4 working connections positioned opposite the supply side. Operating on a single-wiring electrical arrangement without internal fieldbus communication, the assembly utilizes 3/2-way valve functionality to control neutral gases and compressed air within a nominal operating pressure envelope of 2.00 bar to 8.00 bar.

Designed for integration onto standard DIN rails in control cabinets, this valve island integrates multiple sub-base modules into a centralized pneumatic distribution manifold. The pilot stages are operated by low-power solenoid pilot valves, while NBR seals and robust modular bodies ensure tight pneumatic isolation across medium operating temperatures from 0 °C to +50 °C.

BURKERT 20121702 Type 8640 modular pneumatic valve island overview

Valve Island Architecture and Valve Design ​

The pneumatic block integrates modular sub-bases equipped with Type 5470 solenoid valves, driven by Type 6106 pilot valves. Each valve station features internal pilot channeling, diaphragm-seat seals, integrated working ports, and manual override mechanisms.

BURKERT 20121702 Type 5470 solenoid valve internal structure and port identification

ItemDesignation
1Pilot valve Type 6106
2Exhaust port 3 (R)
3Pressure port 1 (P)
4Working port 4 (A)
5Working port 2 (B)
6Manual override
7Cable plug Type 2506 / Type 2516

Manual Override Function ​

Manual operation allows commissioning and functional checks when electrical control signals are de-energized.

BURKERT 20121702 Type 5470 manual override operation mechanism

Operating the Manual Override

To activate the valve manually, press the manual override down and turn it 90° clockwise until it hits the mechanical stop. The override locks mechanically and does not reset automatically. Return it to the 0° zero position before initiating electrical operation.

Pneumatic Port Numbering ​

All pneumatic connections on the Type 8640 island and individual valve slices follow standard numeric markings:

Connection NumberPort Function
1Pressure supply port (P)
2 and 4Working ports (B and A)
3Exhaust port (R)

Circuit Functions and Conversion ​

Depending on the internal configuration and base porting, Type 5470 valve slices support standard directional functions:

  • Function C (3/2-way, normally closed): In rest position, pressure port 1 (P/NC) is closed; working port 2 (A/OUT) vents through exhaust port 3 (R/NO).
  • Function D (3/2-way, normally open): In rest position, pressure port 1 (P/NO) communicates with working port 2 (B/OUT); exhaust port 3 (R/NC) is closed.
  • Function G (4/2-way): In rest position, pressure port 1 (P) feeds working port 2 (A); working port 4 (B) discharges to exhaust port 3 (R).

Converting 4/2-Way Slices to 3/2-Way Operation ​

BURKERT 20121702 port plugging for 4/2 to 3/2-way valve conversion

A 4/2-way valve can be converted to 3/2-way functionality by closing one of the working ports with a dedicated threaded plug or stopper:

Port 2Port 4Resulting Circuit Function
ClosedOpenFunction C (Normally Closed)
OpenClosedFunction D (Normally Open)

Technical Specifications ​

ParameterSpecification
Ident Number (Article Number)20121702
Valve Island Type8640
Number of Valve Stations16-bank
Station Width (Add-on dimension 1)33 mm
Valve Function3/2-way
Pressure Port 1 (P)G 1/2
Working Ports 2 (B) / 4 (A)G 1/4
Nominal Operating Pressure Range2.00 bar to 8.00 bar
Pilot Pressure Requirement2 bar to 10 bar (at least 70% of operating pressure)
Minimum Pressure Differential (Port 1 to 3)2 bar
Medium Temperature Range0 °C to +50 °C (operation below 0 °C restricted to dried air)
Ambient Temperature Range0 °C to +55 °C
MediumFiltered compressed air (particle size max. 10 μm, lubricated or unlubricated); neutral gases (5 μm filtering)
Seal MaterialNBR
Protection ClassIP20 (base unit configuration); IP65 with Type 2516 cable plug correctly fitted
Mounting StandardDIN-rail installation (EN 50022: 35 x 15 or 35 x 7.5)
Voltage Tolerance±10%
Coil Power Rating2 W (standard continuous DC coil)
ApprovalsUL Recognized cURus (pneumatic valves)

Continuous Operation Guideline

If continuous operation is interrupted, perform a minimum of 1 to 2 switching operations per day throughout the downtime to maintain functional switching reliability.

Modular Block Assembly and Mounting ​

Type 8640 valve blocks are assembled modularly by snapping base modules together between dedicated left and right connection modules.

BURKERT 20121702 multi-block modular base interlocking layout

ItemDesignation
1Left connection module
2Latch tab
3Latch hook
4Base modules (3-fold)
5Right connection module
6Base modules (2-fold)
7Exhaust channel 3 (R)
8Supply channel 1 (P)
9Inter-module O-ring

Assembly Sequence and Torques ​

  1. Begin block assembly starting from the left connection module.
  2. Ensure each module interface is equipped with 2 O-rings. Lightly oil or grease all O-rings prior to latching.
  3. Engage the lower latch hooks of the adjoining module into the latch grooves of the preceding unit.
  4. Pivot the module slightly upward until the upper latch hook snaps securely into place.
  5. Fit 3 O-rings into the rear sealing recesses of each Type 5470 valve slice.
  6. Mount each valve body to the base block using two fastening screws. Tighten with a torque of 0.6 ±0.1 Nm.

Sealing Integrity

Crushed, twisted, or missing O-rings and profile seals between modular sub-bases will result in pneumatic leakage across the central channels.

Island Mounting Options ​

BURKERT 20121702 valve island DIN rail and wall mounting installation

  • Standard DIN Rail Installation: Hook the top groove of the valve island onto the standard rail (EN 50022, 35 x 15 mm or 35 x 7.5 mm). Snap the bottom clamping elements onto the rail and tighten the clamp fixing screws.
  • Wall Mounting: Fasten the island connection flanges directly to the mounting panel using M4 screws.
Port Thread SizeFunction / LocationRecommended Torque [Nm]Maximum Torque [Nm]
G 1/4 / NPT 1/4P (Supply), R/S (Exhaust) connections4 to 720
G 1/8 / NPT 1/8P, R/S connections, A/B working ports3 to 67

Pneumatic Installation and Hose Line Guidelines ​

Pressure Hazard

Depressurize and vent all pneumatic lines before commencing installation or servicing. Loose, flapping compressed air lines can cause severe bodily injury.

When connecting pneumatic lines to push-in connectors or threaded ports, adhere to the following hose line criteria:

  • Material Hardness: Minimum 40 Shore D in accordance with DIN 53505 / ISO 868.
  • Outer Diameter: Conforming to DIN 73378 with a maximum tolerance deviation of ±0.1 mm from nominal size.
  • Preparation: Cut hose ends cleanly at a 90° right angle; ensure the outer circumference is free from burrs, scratches, or oval distortion.

Hose Outer Diameter Tolerances (ISO 14743:2020) ​

Hose MaterialHose OD [mm]Permitted Deviation OD [mm]
Polyamide (PA)3 to 10±0.08
Polyamide (PA)12 to 16±0.10
Polyurethane (PU)3 to 8±0.10
Polyurethane (PU)10 to 16±0.15

Minimum Retention Force for Push-In Fittings ​

Pneumatic push-in fittings must withstand the tensile testing values specified in DIN ISO 14743:2020 without detaching:

Hose OD [mm]Hose OD [in]Min. Tensile Force PA [N]Min. Tensile Force PU [N]
31/8 (3.17)6025
45/32 (4.00)7050
61/4 (6.35)120100
85/16 (8.00)170150
103/8 (9.52)250200
121/2 (12.70)300200
14—300250
165/8 (16.00)350300

Hose Support Sleeves

When using softer polyurethane (PU) tubing under high operating temperatures or dynamic movements, install internal support sleeves (ID 20099400) to prevent hose collapse and maintain sealing grip.

Electrical Installation ​

Each solenoid valve station on the single-wired 20121702 island utilizes an industrial standard Form C connection interface.

BURKERT 20121702 Type 2516 cable plug electrical connection assembly

  • Cable Plug Compatibility: Type 2516 or approved connectors according to DIN ISO 175301-803 Form C.
  • Fastening Torque: Tighten the central cable plug screw with a maximum torque of 0.3 Nm (1.0 Nm maximum for coil contact retention).
  • Protective Conductor Verification: Ensure continuous grounding continuity between the coil protective earth contact and the valve body.
Test ParameterRequired Test Value
Earth Contact ResistanceMaximum 0.1 Ω
Test Voltage12 V
Test Current1 A

Impulse Solenoid Control Truth Table ​

For bistable impulse coil variants, observe correct wiring polarity and provide a minimum pulse duration of 50 ms:

Plug Terminal ConfigurationPilot Valve StateFunction WWG Flow PathFunction WWC Flow Path
(+) on pin 2, (-) on pin 1Pilot valve opened1 → 3, 2 → 31 → 4
(+) on pin 1, (-) on pin 2Pilot valve closed1 → 2, 4 → 34 → 3

Troubleshooting and Fault Clearance ​

Fault SymptomProbable CauseCorrective Action
Valves do not switchOperating voltage missing or below toleranceCheck wiring terminals; verify voltage corresponds to the rating on the type label.
Valves do not switchManual override engagedReset manual override to the zero position.
Valves do not switchInsufficient supply pressureEnsure operating pressure is at least 2 bar; check upstream pressure regulators and filters.
Valves switch with delay or exhaust continuouslyInadequate air volume or pressure dropSize air supply lines adequately; verify minimum 2 bar operating pressure.
Valves switch with delay or exhaust continuouslyValve not in home position during pressure buildupApply supply pressure to the valve block before switching electrical controls.
Valves switch with delay or exhaust continuouslyExhaust back-pressure from clogged or undersized silencersClean contaminated silencers or install higher-flow silencers and expansion vessels.
Valves switch with delay or exhaust continuouslyContamination in pilot or main valve seatApply pressure pulses through exhaust ducts to dislodge dirt, or replace affected valve slice.
Pneumatic leaks on valve islandDamaged or missing O-rings between sub-basesInspect module joints; replace damaged or omitted inter-base O-rings.
Pneumatic leaks on valve islandMisaligned flat seal under valve bodyRealign or replace flat gasket between valve body and sub-base.

Disassembly and Auxiliary Feeding ​

  1. Disconnect all electrical connectors and depressurize the pneumatic system.
  2. To release push-in tubing, depress the release collar fully while pulling the hose straight out.
  3. Loosen the rail clamping screws approximately 4 turns and lift the assembly off the DIN rail.
  4. To separate individual sub-base modules, insert a flat screwdriver into the disassembly notch on the front edge to release the upper latch hook, then slide the module sideways.

Dual Pressure and Auxiliary Air Feeding

The right connection module can be utilized in specialized layouts as an intermediate pressure separator, allowing two distinct operating pressure zones on a single island, or as an auxiliary air inlet for high-flow installations. If required, pierce the pre-punched lateral knockout ports on channels 1 and 3.