BURKERT 20114573 8652 AirLINE Valve Island

BURKERT 8652 AirLINE valve island optimized for process automation. Features up to 24 valve slots, AirLINE Quick adapter, PROFINET S2, and ATEX/IECEx Zone 2 approvals.

BURKERT 20114573 8652 AirLINE Valve Island

BURKERT 8652 AirLINE valve island has been developed for process automation requirements. Diagnostic functions can be visualised on the LC display in clear text and symbols, simplifying the assignment of messages and saving time during start-up and maintenance. Diagnostic messages are also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, and installation on a standard rail is also supported. Key pneumatic functions ensure increased process reliability; check valves in the exhaust air ducts prevent unplanned actuation due to pressure peaks.

General Technical Data ​

Product propertiesSpecification
MaterialBody: PA (polyamide)
Seal: NBR and PUR
Width per station11 mm
Manual overrideLatching, spring return (optional: lockable)
Number of valve slotsMax. 24
Maximum valve functionsMax. 48
Pneumatic intermediate supplyOptional for the variants with 16, 20 and 24 valve slots
Pressure rangeVacuum to 10 bar
External supply air3 to 10 bar
Flow rate Qn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power per valve0.7 W (0.175 W after power reduction)
Nominal current per valve29 mA (10 mA after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C to +55 °C

AirLINE Quick ​

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or wall.

Advantages:

  • Reduced space requirement in the control cabinet.
  • Enables the use of more compact control cabinets.
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet.

BURKERT 20114573 BURKERT 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Product propertiesSpecification
AirLINE Quick Adapter PlateStainless steel 1.4301 or Anodised aluminium
Pneumatic connectionStainless steel 1.4401 or Nickel-plated brass
Valve functions per station8, 16, 24, 32, 40 and 48
Pneumatic Supply / ExhaustPush-in D 10 mm, 3/8"
Pneumatic working portsPush-in D 6 mm, 1/4"

Circuit Functions ​

Circuit functionDescription
C (CF C)3/2-way solenoid valve, servo-controlled, normally closed
C (CF C) 2x2 × 3/2-way solenoid valve, servo-controlled, normally closed
D (CF D) 2x2 × 3/2-way solenoid valve, servo-controlled, normally open
H (CF H)5/2-way solenoid valve, servo-controlled. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
L (CF L)5/3-way solenoid valve. In middle position all ports locked.
M (CF M)5/3-way solenoid valve, servo-controlled. In middle position ports 2 and 4 ventilated.
N (CF N)5/3-way solenoid valve. In middle position ports 2 and 4 exhausted.
Z (CF Z)5/2-way solenoid valve. Impulse variant with 2 coils.

SIA Variant (for safety-related shut-off)

SIA variants are available for circuit functions C, 2xC, H, and L. These servo-controlled valves do not require manual override and allow a valve circuit to be interrupted by an external switch.

Approvals and Conformities ​

ApprovalDescription
Explosion protectionOptional: As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc.
North America (USA/Canada)Optional: UL Listed (UL 61010-1). UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
CCCOptional: China Compulsory Certification for hazardous applications in China.

Dimensions ​

Variant 4-, 8- and 12-fold ​

BURKERT 20114573 BURKERT 8652 dimensions for 4-, 8- and 12-fold variants

Variant 16-, 20- and 24-fold ​

BURKERT 20114573 BURKERT 8652 dimensions for 16-, 20- and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116
16-fold without intermediate supply9919810 x M5-15-4
20-fold without intermediate supply12124210 x M5-19-5
24-fold without intermediate supply14328610 x M5-23-6

Product Connections ​

Power supply for communication and displays (5-pin spring-loaded terminal):

  • Red: 24 V DC
  • White: CAN_H (büS connection)
  • Green: SHIELDING
  • Blue: CAN_L (büS connection)
  • Black: GND

Power supply for pneumatic valves (2-pin spring-loaded terminal):

  • Red: AUX 24 V
  • Black: GND

Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) or PROFINET S2 – Interface X1 and X2 RJ45: Pin 1: TX+, Pin 2: TX-, Pin 3: RX+, Pin 6: RX-.

Product Installation ​

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20114573 BURKERT 8652 installation situation inside the control cabinet

Product Design and Assembly ​

BURKERT 20114573 BURKERT 8652 interface plate 24V without modular shut-off

Electronic module with digital inputs (optional) ​

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).

Example Configuration ​

BURKERT 20114573 BURKERT 8652 network configuration example with Industrial Ethernet

Safety Instructions for EX Areas ​

Danger from electrical voltage and electrostatic charge

  • Before working on the device or system, switch off the power supply and secure against reactivation.
  • In an existing explosive atmosphere, the connection terminals for 24 V power supply, SIA, EVS, and digital inputs may only be plugged in or unplugged when the power is switched off.
  • The use of the Hot Swap function is prohibited in an existing explosive atmosphere.
  • Take suitable measures to ensure that no electrostatic charge can build up in the potentially explosive area. Clean the device surface only by wiping it gently with a damp or antistatic cloth.

Ordering Information (Replacement Valves) ​

Solenoid valve Type 6534

Circuit functionNominal diameterQn value AirPressure rangeVoltageArticle no.
C (CF C)4 mm270 l/minVac to 10 bar24 V DC20102334
C (CF C) 2x4 mm270 l/minVac to 10 bar24 V DC301374
D (CF D) 2x4 mm310 l/minVac to 10 bar24 V DC301375
H (CF H)4 mm290 l/minVac to 10 bar24 V DC301376
Z (CF Z)4 mm290 l/minVac to 10 bar24 V DC301377
L (CF L)4 mm275 l/minVac to 10 bar24 V DC301380
M (CF M)4 mm300 l/minVac to 10 bar24 V DC301379
N (CF N)4 mm300 l/minVac to 10 bar24 V DC301381