Skip to content
Balanced PressureCast Bronze BodyMax 125 psig

Armstrong TV-2 Thermostatic Air Vent, Balanced Pressure, Cast Bronze

Armstrong TV-2 balanced pressure thermostatic air vent for positive venting of air from chamber type heat transfer equipment. Features cast bronze body and stainless steel valve.

Armstrong TV-2 Thermostatic Air Vent, Balanced Pressure, Cast Bronze

Armstrong TV-2 Balanced Pressure Thermostatic Air Vent provides positive venting of air from chamber type heat transfer equipment with no loss of steam. Typical applications include jacketed kettles, retorts, vulcanizers, jacketed sterilizers, or other contained equipment where air could accumulate at the top of the steam chamber and reduce heat transfer capacity.

The Model TV-2 responds to the pressure-temperature curve of steam at any pressure from light vacuum to maximum operating pressure. Air is automatically vented at slightly below steam temperature throughout the entire operating pressure range. The thermostatic element is a charged multi-convolution phosphor bronze bellows caged in stainless steel. The valve and seat are also stainless steel, designed to meet the most rigid cycling specifications known for this type of service.

Armstrong TV-2 Thermostatic Air Vent product view

Features

  • Stainless steel hemispherical valve and seat.
  • Thermostatic element comprises a multi-convolution phosphor bronze bellows caged in stainless steel.
  • Thermostatic element is charged with water to provide positive opening of the valve at slightly below steam temperature and positive closing in the presence of steam throughout the operating pressure range.
  • ASTM B62 cast bronze body.

Materials

Name of PartMaterial
Body & CapCast bronze ASTM B62
GasketCompressed non-asbestos
Thermostatic Unit Bellows Cage and CoverPhosphor bronze, Stainless steel
Thermostatic Unit GasketCopper clad

Physical Data

SpecificationValue
Pipe Connections3/8", 1/2" (10 mm, 15 mm)
"A" (Diameter)2-3/16" (56 mm)
"B" (Height)3-1/2" (89 mm)
Weight1 lb. 9 oz. (0.8 kg)
Maximum Operating Pressure125 psig (9 bar)
Maximum Temperature350°F (177°C)

Armstrong TV-2 dimensional drawing and physical data

Installation

Armstrong Model TV-2 Thermostatic Air Vents should be installed at the highest points of steam chambers with inlet connections to the vents higher than the highest points of the chambers. Thus installed, there is a minimum hazard of any liquid carryover and air can be vented to atmosphere with no drain line necessary.

Typical Installations

Armstrong TV-2 installation on a retortFig. 2-1. Installation on a retort.

Armstrong TV-2 installation on a sterilizerFig. 2-2. Installation on a sterilizer.

Armstrong TV-2 installation on a vulcanizerFig. 2-3. Installation on a vulcanizer.

Armstrong TV-2 installation on jacketed kettlesFig. 2-4. Installation on jacketed kettles.

Maintenance and Safety

Equipment under pressure